NFPA 10

Fire Extinguisher Inspection & Recharge

Commercial fire extinguishers need a documented annual service by a qualified technician, plus a quick visual check by your own staff every month. Redbird handles the annual service, the 6-year internal maintenance, hydrostatic testing, recharge, and the tagging that proves it was done.


What it involves

The work itself

  • A physical check of every extinguisher on the property: pressure, seals, pull pins, hoses, horns, and mounting height.
  • Verifying each unit is the correct type and rating for the hazard near it. A kitchen line needs a Class K unit; a server room does not want dry chemical.
  • Weighing and inspecting cartridges, replacing tamper seals, and recharging any unit that has been discharged or has lost pressure.
  • Internal maintenance at 6 years and hydrostatic testing at 12 years for most dry chemical units, tracked so you are not guessing which units are due.
  • A dated tag on every extinguisher and a written report listing every unit by location, so an inspector can verify compliance without a scavenger hunt.
How often it is required

Required intervals

IntervalWhat happensWho does it
MonthlyA quick visual check that each unit is present, unobstructed, fully charged, and undamaged. This one is on your staff and takes minutes.Building staff
AnnuallyA full maintenance inspection by a qualified technician, with a new tag and a written record.Redbird
Every 6 yearsInternal examination of most stored-pressure dry chemical extinguishers. The unit is emptied, inspected inside, and recharged.Redbird
Every 12 yearsHydrostatic pressure testing for most dry chemical cylinders. Some units, including Class K and CO2, run on a 5-year cycle.Redbird

These intervals come from NFPA 10. Your local fire marshal can require more, and your insurer or lease can too. If you are unsure what applies to your building, call us and we will tell you straight.

What a visit looks like

When we show up

  1. 01

    We walk the property and inventory every extinguisher by location, type, and size.

  2. 02

    Each unit gets inspected, serviced, and tagged on the spot. Units needing recharge or internal work are handled or swapped so you are never left with an empty bracket.

  3. 03

    We flag anything that is missing, mismounted, obstructed, or wrong for the hazard it sits next to.

  4. 04

    You get a report the next business day listing every unit, what we did, and anything still open with a recommended next step.

Common questions

Straight answers

How often does a fire extinguisher need to be inspected in Texas?
Commercial fire extinguishers need a visual inspection every 30 days by building staff and a full maintenance inspection every 12 months by a qualified technician, per NFPA 10. Beyond that, most dry chemical units need internal maintenance at 6 years and hydrostatic testing at 12 years. Your local AHJ can require more.
Who can perform the monthly extinguisher check?
Your own staff can do the monthly visual inspection. It is a check that the extinguisher is present, visible, unobstructed, fully charged, and undamaged. The annual maintenance inspection is different and must be done by a qualified technician.
What happens if an extinguisher fails inspection?
It depends on what failed. A low-pressure gauge or a broken seal usually means a recharge. Physical damage, corrosion, or a failed hydrostatic test means the unit is removed from service and replaced. We tell you which it is, and we do not leave a location unprotected while it is sorted out.